Product Center

ZW8-12 Vacuum Circuit Breaker

Short Description:

The ZW8-12 outdoor high-voltage vacuum circuit breaker is a high-voltage outdoor switchgear with a rated voltage of 12kV and a three-phase AC 50Hz. It is mainly used to switch the load current of rural power grids, urban power grids and small power systems.

Material: Procelain,copper,hot dip Galvanized steel and SF6 air


  • Product name: 12kV Vacuum circuit breaker
  • Type: Type
  • Rated voltage: 12KV
  • Rated current: 630A
  • Standard: IEC60056,IEC60265
  • Material: Procelain,copper,hot dip Galvanize
  • Rated frequency: 5060Hz
  • Application: power station
  • Mechanical Life: 10000
  • Packing: Wooden Case
  • Product Detail

    Product Tags

    Specification

    Serial number

    parameter name

    Value

    1

    Rated voltage

    12KV

    2

    Rated current

    630A

    3

    Power frequency withstand voltage

    42kV/48kV

    4

    Mechanical life

    10000

    5

    Isolation new port disconnect distance

    > 200mm

    6

    Average opening speed

    1.0+0.2m/s

    7

    Average closing speed

    0.7+0.15m/s

    Parameter

    Rated voltage

    KV

    12

    Max. operating voltage

    KV

    12

    Rated current

    A

    630

    Rated short circuit load breaking current

    KA

    20

    Rated short circuit making current (peak)

    KA

    50

    Rated p-eak withstand current

    KA

    50

    Rated short time withstand current 1 min

    KA

    20

    Rated insulation Power

    level

    Power frequency withstand voltage (dry) 

    KV

    42

    Lig htning impulse withstand voltage (peak}

    KV

    75

    Rated operating sequence

     

    (O)-0.3s{CO)-180s (CO)

    Mechanical life

    time

    10000

    Nos of breaking rated short circuit breaking current

    time

    30

    Rated dosing voltage of operating mechanism

    V

    110,220

    Rated opening voltage of operating mechanism

    V

    110,220

    Opening distance of contact

    mm

    11 ±1

    Over travelling distance (spring compressed length of contact}

    mm

    3

    Asynchrony of opening or closing three phases

    ms

    ≤2

    Jumping time of contact closing

    ms

    ≤2

    Average opening speed

    s

    1.0±0.2

    Average closing speed

    s

    0 7±0.15

    Opening time

    Under highest operating voltage

    s

    0.015-0.05

    Under lowest operating voltage

    s

    0.03-0.06

    Closing time

    s

    0.025-0.05

    Main circuit resistance of each phase

    卩C

    ≤120

    Permissible abraded thickness of moving and static contacts

    mm

    3


  • Previous:
  • Next:

  • Write your message here and send it to us