We have now numerous great personnel members good at advertising, QC, and working with kinds of troublesome dilemma from the creation course of action for 33kv Live Tank SF6 Outdoor Circuit Breaker 630A 1250A 1600A, Our clientele mainly distributed within the North America, Africa and Eastern Europe. we are able to supply premium quality goods with the incredibly aggressive price tag.
We have now numerous great personnel members good at advertising, QC, and working with kinds of troublesome dilemma from the creation course of action for SF6 Outdoor Circuit Breaker 630A, We guarantee that our company will try our best to reduce customer purchase cost , shorten the period of purchase , stable products quality , increase customers’ satisfaction and achieve win-win situation .
Rated Voltage | 36KV |
Rated Current | 800/1600/2500 / 3150/4000 |
Mechanical Life | 10000 times |
SF6 Gas rating(Gage pressure whenthe 20 °C) | 0.45Mpa |
Lock pressure(Gage pressure whenthe 20 °C) | 0.4Mpa |
Minimum ambient temperature | -40°C |
Rated short circuit duration | 4S |
Item |
Unit |
Data |
Maximum Voltage |
KV |
40.5 |
Rated voltage |
KV |
36 |
Rated Current |
A |
1250 |
Lightning Impulse withstand Voltage (Full Crest Value) |
KV |
185/215 (fracture) |
Power Frequency Withstand Voltage |
KV |
95/118 (fracture) |
Rated short-circuit breaking current |
KA |
31.5 |
Rated short circuit closing current (peak) |
KA |
80 |
Rated out-of-step breaking current |
KA |
8 |
SF6 gas pressure rating (20℃ gage pressure) |
Mpa |
0.45 |
Closure pressure(20℃ gage pressure) |
Mpa |
0.4 |
yearly gas leakage rate |
%/year |
≤0.1 |
SF6 gas moisture content(20℃) |
ppm(v/v) |
≤150 |
Turn-off time (under rated operating voltage) |
ms |
≤50 |
Closing time (under rated operating voltage |
ms |
≤100 |
Conductive loop resistance of each phase |
μΩ |
≤80 |
Rated operation sequence |
V |
Points—03s—or points-180s—or points |
Control Voltage |
KG |
DC;110V DC;220V |
SF6 gas weight |
KG |
6 |
Breaker weight (including operating mechanism |
|
800 |
LW36-40.5 Outdoor AC 50HZ sulfur hexafluoride circuit breakers for three-phase power system of outdoor equipment, for industrial and mining enterprises, power plants and substations for control and protection. The product can be frequent operation can be used as contact breakers and meet the capacitor, circuit breaker with reactor group. Containing a current transformer for measurement and protection, can directly replace SW2-35-type breaker, with various models of transition support alternative multi-oil circuit breakers, 35kV power system is the ideal non-oil circuit device.
LW36-40.5 circuit breaker equipped with the CTl4-A type of AC-DC dual-spring mechanism. 1.3 LW36-40.5-type circuit breakers meet the IEC 62271.