The key to our success is "Good Product Quality, Reasonable Value and Efficient Service" for Loose Breaker Switch, Vcb Breaker In Hindi, Double Breaker Switch, Special emphasis around the packaging of merchandise to avoid any damage during transportation,Detailed interest into the useful feedback and strategies of our esteemed shoppers.
OEM High Quality Revit Prefabricated Substation Suppliers – GW4-12(40.5) L&R 12kV Outdoor disconnecting switch isolating switch with earth disconnecto Outdoor HV Disconnect Switch – L&R Detail:

Specification

1. Altitude:≤3000m;

2. Ambient temperature:-25°C ~ +40°C;

3. Wind speed:≤35m/s;

4. Pollution degree:≤III

5. Earthquake intensity.≤8 degree;

6. Applicable occasions should free from infiammable, explosives caustic gas.

Parameter

No.

Product model→

GW4-40.5III

GW4-72.5III

GW4-126 III

Rated value↓

1

Rated voltage

40.5

72.5

126

2

Rated current

630

1250

1600

2000

630

1250

1600

2000

630

1250

1600

2000

3

Rated withstand current (peak value)

50

80

100

100

50

80

100

100

50

80

100

100

Rated short time withstand current (effective value) kA

20

31.5

40

40

20

31.5

40

40

20

31.5

40

40

Duration of rated short ciruit (s)

4

4

Rated withstand current (peak value)

25

Rated short-time withstand current (effective value) kA

10

Duration of rated short circuit (s)

4

5

Rated withstand current (peak value)

100

Rated short-time withstand current (effective value) kA

40

Duration of rated short circuit (s)

4

6

Rated short-time power frequency withstand voltage (effective value)kV

To earth

95

160

230

Across the isolating distance

118

197

265

7

Rated lightning impulse withstandvoltage (effective value)kV

To earth

185

350

550

Across the isolating distance

215

385

630

8

Rated terminal static mechanical load N

Level vertical

750

750

750

750

750

750

Level horizontal

500

500

500

500

500

500

Vertical force

500

500

500

500

500

500

9

Switch generator conversion current(generatrix conversion voltage 100V)A

504

1000

1280

1600

504

1000

1280

1600

504

1000

1280

1600

10

Wireless electricity disturbing level

no

no

Not over2000pV

11

Mechanical endurance

3000

3000

3000


Product detail pictures:


Related Product Guide:

Often customer-oriented, and it's our ultimate target to become not only probably the most reputable, trustable and honest provider, but also the partner for our customers for OEM High Quality Revit Prefabricated Substation Suppliers – GW4-12(40.5) L&R 12kV Outdoor disconnecting switch isolating switch with earth disconnecto Outdoor HV Disconnect Switch – L&R , The product will supply to all over the world, such as: Cyprus, British, Mexico, Being the top solutions of our factory, our solutions series have been tested and won us experienced authority certifications. For additional parameters and item list details, please click the button to acquire additional nformation.
Goods just received, we are very satisfied, a very good supplier, hope to make persistent efforts to do better.
5 Stars By Marjorie from Iraq - 2017.08.28 16:02
The customer service staff's answer is very meticulous, the most important is that the product quality is very good, and packaged carefully, shipped quickly!
5 Stars By Juliet from Stuttgart - 2017.10.13 10:47
Write your message here and send it to us