1.The trinity of high-voltage switchgear, transformer and low-voltage switchgear has a strong complete set
2.The high and low voltage protection is perfect, the operation is safe and reliable, and the maintenance is simple;
3. Small area, low investment, short production cycle and convenient movement;
4. The wiring scheme is flexible and diverse;
5. Unique structure: the unique honeycomb structure double-layer (composite board) shell is firm, heat-insulating, heat-dissipating and ventilating, beautiful, and high-level of protection. The shell materials are stainless steel alloy, aluminum alloy, cold-rolled plate, and color steel plate.
6. Variety of styles: general, villa, compact and other styles;
7. The high-voltage ring network cabinet can be equipped with a network automation terminal (FTU) to realize the reliable detection of short-circuit and single-phase grounding faults. It has the "four remote" function, which is convenient for the automatic upgrade of the distribution network.
1. Altitude: not more than 1000m;
2. Ambient temperature: -25℃-+40℃;
3. Relative humidity: the daily average value is not more than 95%.;The monthly average value is not more than 90%;
4. Installation site: A place free from fire, explosion hazard, conductive dust, chemically corrosive gas and severe vibration. If the above conditions are exceeded, the user can consult with our company.
Main technical parameters |
|||
HV unit |
Rated frequency |
Hz |
50 |
Rated voltage |
kV |
7.2 12 24 40.5 |
|
Rated current of main bus |
A |
630 1250 1600 |
|
Rated short-time withstand current / duration |
kA/s |
20/4 25/3 31.5/4 |
|
Rated peak withstand current |
kA |
50 63 80 |
|
1min power frequency withstand voltage (to-ground/between open contacts) |
kV |
32/36 42/48 65/79 95/115 |
|
Lightning impulse withstand voltage (to-ground/between open contacts) |
kV |
60/70 75/85 125/145 185/215 |
|
Rated short-circuit breaking current |
kA |
20 25 31.5 |
|
Ground loop short-time withstand current / duration |
kA/s |
20/2 20/4 |
|
Rated short-circuit making current of main loop |
kA |
50 63 80 |
|
Rated active load breaking current |
A |
630 |
|
Rated closed loop breaking current |
A |
630 |
|
Rated transfer current |
A |
1700 |
|
Mechanical life peroid |
times |
3000 5000 10000 |
|
LV unit |
Rated frequency |
Hz |
50 |
Rated voltage |
kV |
0.4/0.23 |
|
Rated insulation voltage |
V |
690 |
|
Rated current of main loop |
A |
100~3200 |
|
Rated short-time withstand current |
kA/s |
30/1 50/1 100/1 |
|
Rated peak withstand current |
kA |
63 105 176 |
|
5s power frequency withstand voltage |
kV |
2.5 3.75 |
|
Transformer unit |
Rated frequency |
Hz |
50 |
Rated voltage |
kV |
7.2 12 24 40.5/0.4 |
|
Rated capacity |
kVA |
30~1600 |
|
1min power frequency withstand voltage |
kV |
25/20 35/28 55/50 85/75 |
|
Lightning impulse withstand voltage |
kV |
60 75 125 170 |
|
Impedance voltage |
% |
4~6 |
|
Tapping range |
... |
±×2.5% ±×5% |
|
Connection group |
... |
Y,yn0 D,yn11 |
|
Type |
... |
Oil-immersed type, dry type |
|
Cabinet body |
IP code of HV and LV chambers |
... |
IP33D |
IP code of transformer chamber |
... |
IP23D |
|
Sound level (oil-immersed type/dry type) |
dB |
≤50/55 |
1. The following information must be provided when ordering:
2. Type and quantity of substation;
3. Type and quantity of transformers;
4. High-voltage and low-voltage primary wiring schemes and the models and parameters of main components;
5. The material and color of the housing.
Q1: Are you factory?
A. Yes, We have 3 factories.
Q2: Are the samples free?
A: Most are free, some items need discuss.
Q3: What kind of payment do you accept?
A: We accept T/T,L/C. PAYPAL. WESTERN UNION
Q4: Are you always available?
A: Yes i am online even in holiday! I will try my best to make you satisfied, If you need any help in china, please contact me. We are your right choice