Product Center

Pole-mounted porcelain Air breaker switch

Short Description:

The GW1 switch is a double-column outdoor high-voltage isolation switch composed of three single poles. The switch is a one-way opening type. It consists of a base, an insulator, a contact knife guide and a conductive part. On both sides of the base, there are tie-rod insulators, a crank arm and a rotating shaft in the middle to open or close the switch. The switch can be equipped with an anti-theft operating mechanism or a common operating mechanism.


Product Detail

Product Tags

General

GW1 outdoor AC high voltage isolation switch is suitable for installation on the line of outdoor high voltage power distribution equipment for the purpose of cutting off the line and converting the line when the line has voltage and no load. This product is a three-phase electrical appliance consisting of three separate single-pole isolating switches. Each single-pole isolating switch has the same components, such as base pillar insulator, front and rear static contacts, knife and arc angle, etc.

Service and Installation Conditions

image2

Environmental conditions:
1. The altitude should not exceed 2000m.
2. The upper limit of ambient temperature is +40℃, and the lower limit is -30℃ in general areas.
3. The wind pressure does not exceed 8 degrees.
4. The earthquake intensity does not exceed 8 degrees.
5. The thickness of ice coating is not more than 1mm.
6. There is no frequent violent vibration in the installation site.
7. Gas, steam, chemical deposits, salt spray, dust and other explosive and corrosive substances that seriously affect the insulation and conductive fertility of the isolating switch should be installed in ordinary installation sites.
8. The anti-fouling type is suitable for heavily polluted areas, but should not be used to cause superfluous fire and explosion.

Model and Definitions

1662712035643
image3

Technical parameters

Rated Voltage

kV

Rated Current

A

Rated short-circuit current

kA

4S Thermally stable current

KA

Dynamic stable current

kA

Lightning impulse withstand voltage

kV

1 minute power frequency withstand voltage

kV

Grouding

isolated

Grouding

isolated

11

400

16

12.5

31.5

95

115

52

48

15

400

16

12.5

31.5

125

135

50

60

24

400

16

12.5

31.5

145

160

58

70

33

630

16

12.5

31.5

185

215

75

85

image4